Audible noise and losses in variable speed induction motor drives with IGBT inverters-Influence of design and the switching frequency | Introduction | Audible
Noise | Losses | Motor and Inverter Used | Measuring
Set-up | Measurements and Conclusions | Acknowledgement | References | ABSTRACT
The use of variable speed drives has gained increasing importance during the last years. For small and medium sized drives, PWM voltage source inverters are the standard type of equipment nowadays. Until a few years ago, the highest switching frequencies available were offered by Power-MOSFET inverters. However, their rated power was modest. Bipolar transistors could be used for higher power rating, but had a lower stitching frequency, The IGBT based inverters combine the advantages of both power electronic components: High switching frequency and high power ratings. Power ratings up to several hundreds of kVA are available commercially. The switching frequency may be several kHz.
The paper describes a large number of experiments comparing audible noise, losses and efficiency of induction motors supplied by an IGBT inverter or directly from the mains. The switching frequency of the IGBT PWM inverter is varied in order to study the influence of this parameter on the motor behavior. Furthermore, two motors are compared. The first motor is a standard induction motor with cast aluminum double squirrel cage rotor. The second motor has a copper cage, with round bars to avoid current redistribution; furthermore the bars are insulated with respect to the rotor iron in order to avoid extra losses, which are difficult to incorporate in the theoretical analysis.
The theoretical analysis of the audible noise starting from the design parameters of the motor, especially the number of stator and rotor slots, and the frequency spectrum of the voltage supplied by the inverter, yields its frequency spectrum. It is shown that the transition of the PWM pattern is the most important factor in the audible noise. Furthermore, the analysis shows under which circumstances pure tones in the spectrum of the audible noise may be expected. This is very important as the human ear is very susceptible to these pure tones: the same audible noise level is experienced being 10 dB(A) higher when it contains pure tones. Due to the harmonics in the inverter voltage and current, the losses in the rotor increase as a result of the skin effect [5]. The currents induced by the higher voltage harmonics are concentrated in the upper part of the rotor bars. Therefore, the efficiency decreases due to these losses. In conventional inverter supplied drives using low switching frequencies , these extra losses are high and the manufacturers of drives prescribe generally a 10 % derating of the motor in order to limit excessive heating. However, practical experiments showed that a 10 % derating sometimes is not sufficient [5,6,7]. The higher switching frequency of modem inverters lead to a lower harmonic content, especially at low speeds. Therefore, the increase in the losses is less pronounced at low speed. However, in pump and fan drives, the output power is limited at low speed. Therefore, the efficiency gain is large, without yielding large power or energy savings. If a constant torque as a function of speed has to be delivered to the load, the power is proportional to the speed. The gain is larger at lower speed than in pump and fan drives. IV. MOTOR AND INVERTER USED As these starting problems are not present in inverter supplied machines, a motor with no current redistribution is no real problem and would lead to less additional losses if the motor is supplied with a non sinusoidal voltage. In order to assess the influence of the current redistribution in the rotor, a special rotor for a standard 13.5 kW machine is built with round rotor bars. The area of the rotor bars is chosen in such a way that the torque and the losses at rated speed are the same as in the standard design. Copper is used as the material for the bars. Interbar currents are avoided by insulating the bars with respect to the rotor iron. The number of rotor bars is kept the same and the stator is a standard construction. No skewing is applied. Both standard rotor design and new rotor are accounted for in the analysis. The inverter is a standard inverter with IGBTS. The switching frequency of the components can be chosen from I to 12 kHz. The tests are done in the normal operation mode, i.e. keeping the Volts/Hertz ratio constant. As a comparison the motors are directly coupled to the mains. The use of a pure sinusoidal supply yields an absolute target for inverter manufacturers, as this is the ultimate optimum regarding frequency content. Using these combinations the influence of the most important parameters on both losses and audible noise are studied. V. MEASURING SET-UP
A torque transducer is used to couple both machines. The transducer contains strain gauges, that are linked with the stationary recording equipment using a frequency modulated transmitter system. These measurements yield a very high accuracy of the torque, far better than the reaction torque often used as an alternative. Also non-steady state torque components and torsional vibrations may be accounted for. In the torque transducer a speed transducer is incorporated, yielding the mechanical power by multiplication. The accuracy of the output power is better the 0.5 %. The input -power is measured with an accuracy of 0.2 % using special power, voltage and current measuring equipment For the assessment of the electrical power between the inverter and the motor, special attention has to be paid to the equipment used. The harmonics in both current and voltage prevent the use of standard power measuring .equipment The frequency spectrum of the power measuring equipment goes up to 200 kHz, in order to account for the power produced by the higher harmonics. The accuracy of the power between inverter and motor is 0.5 %. All efficiency measurements are carried out after thermal equilibrium is reached in the motor. Therefore the motor is loaded during more than one hour with rated power at rated speed before the experiments are started. In the specially designed machine the temperature is monitored and measured using Pt-100 (Platina resistors) sensors. At rated speed and load, the temperature when supplying the motor with the inverter is compared with the temperature when the motor is coupled directly with the supply, in both cases loaded with rated power. The temperature gives a direct indication of the required derating, if any. VI MEASUREMENTS AND
CONCLUSIONS A Overall audible
noise level Conclusions:
Several audible noise spectra have been analyzed for both motors. Only two spectra will be discussed here: the spectrum for the 22 kW motor at a fundamental frequency of 5Hz, a switching frequency of 6kHz and a load of I 00 Nm (Fig. 3) and the spectrum for the13.5 kW motor at a fundamental frequency of 45.05 Hz, a switching frequency of 5 kHz and a load of 75 Nm (Fig. 4).
Around 5 kHz also some large components appear in the audible noise. They are caused by space harmonics of the rotating field. These space harmonics cause vibrations and audible noise. If the frequency of the vibrations is the same as one of the natural frequencies of the stator, there is a large audible noise production.
Because the motor bars
are not skewed, the rotor harmonics are not suppressed so
they yield a lot of vibrations. The frequencies of these
vibrations may be calculated [8]: In this case the motor has 28 rotor bars, a speed of 1318 t/min and 4 pole pairs. At a fundamental frequency of 45.05 Hz the motor has a slip of 2.48%. Applying (1) and (2) for g2 = *9 one can calculate that there should be vibrations at 5626 Hz, 5445 Hz and 5563 Hz. At 5536 Hz there is also a resonance frequency of the stator. Therefore, at a fundamental frequency of 45.05 Hz and a speed of 1318 t/min there is a spike of 78 dB at 5536 Hz at all switching frequencies. At the switching frequency of 5 kHz as shown in Fig. this spike is even 86 dB because of the interaction of a vibration caused by a winding harmonic and a vibration caused by a time harmonic of the voltage spectrum. The harmonics of the voltage system cause also vibrating forces, yielding audible noise. In the voltage spectrum of Fig. 4 there is a time harmonic at 5488 Hz. As the fundamental frequency is 45 Hz, the vibration frequency is 5533 Hz- Taking the accuracy of the measurements into consideration, this frequency equals to the resonance frequency of the stator and with a vibration frequency caused by a winding harmonic. The pure whistle tone of 86 dB in the audible noise spectrum of Fig. 4 is caused by the accidental coincidence of 3 effects at 5536 Hz:
Clearly such a situation
should be avoided by all means.
The type of motor used is also important: motors experiencing a large amount of current redistribution in the rotor during when supplied from the mains cause extra losses with inverter supply as the high frequency currents are concentrated in the upper portion of the rotor bars. To analyze the influence of the rotor lay out two motors of the same rated power arc compared (one with an aluminum skewed double cage rotor and one with a rotor having non skewed copper bars.
TABLE I
A comparison is also made between the two different motors of 13.5 kW and between mains supply and inverter supply at 5OHz- The overall losses are represented in table II. In fig. 6 the different losses are represented as a function of the switching frequency.
The same measurements were repeated for the 22 kW standard motor and again the optimal switching frequency concerning the motor losses is found to be 4 kHz.
The lower voltage in the second case decreases the flux level and therefore less audible noise is produced. The harmonic losses are also lower because of the improved spectrum of the voltage but the motor losses are larger because the currents have to increase to match the required power. The inverter losses also increase. Other disadvantages are a decrease in speed and less dynamic response for torque variations.
Fig. 8 Load curves for continuous load of IEC 34 motors Switching frequency 3 kHz. These curves are valid if the fundamental frequency at the point of field weakening is 50 Hz. If the fundamental frequency is higher than 50 Hz, the torque decreases as the voltage is kept constant as the frequency rises. Therefor the flux and the torque decrease. At lower fundamental frequencies the torque decreases due to a lack of cooling. Therefore with the inverter used between a fundamental frequency between 40 Hz and 50 Hz, the motor can deliver its rated torque. The temperature rise at a fundamental frequency should not be higher than with the main supply. The temperature in the stator winding is measured with embedded Pt - 100 temperature sensors. Table III gives the temperate rise when the motor is operating at a fundamental frequency of 50 Hz, supplied by the inverter at a switching frequency of 3 Hz and 12 kHz and directly by the mains, at a load torque of 70 Nm TABLE
III
The same measurements have also been done for other loads, yielding comparable results. It may be concluded that for the motor and inverter combination used is these tests derating is not necessary. It is dangerous to generalize this conclusion for all motor-IGBT inverter combinations because only the temperature in the stator is measured. Furthermore these measurements were carried out on a single squirrel-cage rotor motor with a specialty built rotor.
[1) R.Belmans, L.DHondt, A.Vandenput, W.Geysen: "Analysis of the audible noise of three phase squirrel cage induction motors supplied by inverters," IEEE Trans. on Industry Applications, September-/October 1987, Vol.IA-23, pp.842-847. [2) R.Belmans, D.Verdyck, W.Geysen, R.Findlay: "Electromechanical analysis of the audible noise of an inverter-fed squirrel-cage induction motor," IEEE Transactions on Industry Applications, Vol-27, No.3, May/June 1991, pp.539-544. [3] R.Belmans, W-Geysen, G.Bailly, P-K.Sattler: TheoreticaI and experimental analysis of the audible noise of an inverter fed squirrel cage induction motor," International Conference on Electrical Machines (ICEM), Cambridge, Massachusetts, USA., August 13-15, 1990, pp.485-490. [4] R.Belmans, D.Vcrdyck, T.-B.Johansson, W.Geysen: "Comparison of starting conditions of induction motors fed from an infinite bus and current source inverter using finite element calculations," Proceedings of the Fourth European Conference on Power Electronics and Applications, Firenze, Italy, September 3-6, 1991, pp.2.375-2.378. [5] R.Belmans, D.Vermeulen, A.Vandenput, W.Geysen: "Economy of the introduction of adjustable speed drives for pumps, fans and compressors," Conference record on the 1986 IEEE-IAS Annual Meeting, September 28-October 3, 1986, Denver, U.S.A., pp.321-327. [6] R. Belmans, D.Vermeulen, A.Vandenput, W.Geysen: "Techno-economical analysis of inverter fed pump drives," Second European Conference on Power Electronics and Applications, EPE, 22-24 September 1987, pp. 1003-1008 [7]
E.Lajoie-Maznec, D.Pratmarty: "Etat de l'offre
europeene de convertisseurs de frequence pour machines
asynchrones", Electricite de France, Direction des
Etudes et Recherches, Mars 1993
Document D-7168-1 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||