AC Drives
|
"Super"
Remote Meter
Interface Card
Optional card expands the input/output
capabilities for applications requiring hardwired
speed/torque and logic control |
 |
Input | Outputs | PI
Regulator | Wiring Diagram
| Mounting Connections
| Customer Benefits
The GV3000 AC Drive is designed with the flexibility
to perform in applications that require either vector or
general purpose control of motor speed and torque. This
flexibility may be enhanced by the inputp/output logic
and control signals provided by the "Super Remote
Meter Interface (RMI) Card.
Inputs
The "Super" RMI
adds these inputs/ouputs to the GV3000:
- Four Isolated
Digital Inputs (24 VDC rated) These inputs may be
used to select:
- up to eight
preset speeds
- select
either analog or frequency input
- enable the
PI regulator
- select
between the GV3000 terminal strip speed
reference or the RMI speed reference turn
any digital output or relay output on and
off with an on-delay or off-delay
time
- One Isolated Analog
Input (O to 10 VDC or 4 to 20 niA selectable; 12
bit resolution) this input may be used as one of
the following:
- either a
speed or trim reference
- the feedback
signal for the outer loop PI regulator
- the source
for torque or current limit
settings.
- One Isolated
Frequency Input (O to 200 kHz; 15 VDC)
This input may be used as either:
- a speed or
trim reference
- the source
for torque or current limit
settings.
Outputs
- Four Isolated
Digital Outputs (24 VDC rated)
- One Output
Relay (I N.O. only rated 250 VAC/24 VDC)
- Two Output Relays (I
N.O. - I N.C. rated 250 VAC/24 VDC)
Digital and relay output signals may be used to
indicate:
- Drive
running
- Drive fault
- Auxiliary input
on or off with time delay
- Run speed
greater than or equal to speed level 1, 2, or
3
- Low speed
detected
- Speed
reached
- Remote mode
(P.000 LOCL)
- Output current
greater than or equal to current level 1, 2,
or 3)
- D-C Braking
active
- Reverse
rotation
- Torque greater
than or equal to torque detection level 1, 2,
or 3)
- Speed regulation
active
Each output signal can be
used with an on-delay or off-delay timer of up to 999.9
seconds)
- Three Isolated
Analog Outputs (O to 10 VDC; -10 VDC to +10 VDC;
0 to 10 VDC or 4 to 20 mA, 10 bit resolution)
Analog output signals may be used to
indicate:
- Motor
Voltage
- Motor
Current
- Speed
reference
- Motor speed or
frequency
- Motor torque
Motor power kW D-C bus voltage
- PI regulator
output
PI
Regulator
The RMI has a built in
Outer Loop Proportional-Integral (PI) Regulator which can
be used as a trim speed reference.
Wiring
Diagram
 |
41 |
|
Digital Input 1 |
 |
42 |
|
Digital Input 2 |
 |
43 |
|
Digital Input 3 |
 |
44 |
|
Digital Input 4 |
 |
45 |
|
+24 V (for digital inputs only) |
 |
46 |
|
External +24 V Input for Digital Outputs |
 |
47 |
|
Digital Output 1 |
 |
48 |
|
Digital Output 2 |
 |
49 |
|
Digital Output 3 |
 |
50 |
|
Digital Output 4 |
 |
51 |
|
Digital Output Common |
 |
52 |
|
Relay 1 Common |
 |
53 |
|
Relay 1 Normally Open |
 |
54 |
|
Relay 2 Normally Closed |
 |
55 |
|
Relay 2 Common |
 |
56 |
|
Relay 2 Normally Open |
 |
57 |
|
Not Used |
 |
58 |
|
Relay 3 Normally Closed |
 |
59 |
|
Relay 3 Common |
 |
60 |
|
Relay 3 Normally Open |
 |
61 |
|
Not Used |
 |
62 |
|
Analog Input: 0 to 10 V |
 |
63 |
|
Analog Input: 0 (4) top 20 mA |
 |
64 |
|
Analog Input Common |
 |
65 |
|
Analog Output 1: 0 to 10 V |
 |
66 |
|
Analog Output 2: +/-10 V |
 |
67 |
|
Analog Output 3: 0 to 10 V/0 to 20 mA |
 |
68 |
|
Analog Output Common |
 |
69 |
|
Frequency Input (Ground = Analog Input
Common) |
Mounting/Connections
Connection to the GV3000
regulator board is made by a flat ribbon cable connector
which is standard with the "Super" RMI Card.
This card mounts inside the GV3000, so that additional
panel space is not required.
Other communication
cards cannot be used when the "Super" RMI Card
is installed.
The standard GV3000
input/output configuration has:
- Standard
Digital Inputs (24 VDC rated) for:
- start-stop
- reset
- function
loss
- three
programmable for: preset speeds,
2nd accel/decel, local/remote,
forward/reverse
- MOP speed
select
- Standard Analog
Input (O to 10 VDC or 4 to 20 mA selectable; 10
bit resolution)
- speed or
torque(vector only) reference
- Standard Relay
Output (I N.O. - I N.C. rated 250 VAC/30 VDC at 5
A resistive or 2 A inductive)
- Programmable to
indicate one of the following:
- drive
fault
- drive
running
- network card
active
- Standard Analog
Output (O to 1 0 VDC or 4 to 20 mA selectable)
Programmable to indicate either:
- output
speed
- output
current
Customer Benefits
Benefits of using
"Super" RMI:
- Expands I/O for
optimum flexibility so more application needs are
met.
- Takes no additional
panel space which keeps installation costs
down.
- PI regulator can
replace separate set point controller which
reduces hardware costs.
- Can obtain more
diagnostics from GV3000 which eases monitoring
and troubleshooting.