AC
Drives |
About This
Guide
This procedure
is a supplement to and to be used in conjunction with the
Installation and Operation Manual for the SP500 Manual
for the SP500 AC Controller I/M D233041. The
procedure is meant to explain and condense the
installation and operation manual to the basic and most
used applications.
|
Hardware | Power
Off
| Power On | | Software | Parameter
List
|
Hardware
Drive
Protection
Input Voltage
and Motor wiring should be sized in accordance with
NEC/CEC and all other local codes. Input fuses should be
provided to meet NEC/CEC and all other local codes.
Suggested protection is a fused disconnect as described
in Section 3.7 of the I/M.
Wiring
Threephase
incoming AC shall be wired to terminals R, S and T (as
shown in figures 1 & 2). Singlephase AC shall
be wired to terminals R and S. AC input wiring, motor
wiring and control wiring should be run in separate
conduits. Drive chassis ground and motor frame ground
wires should be tied to earth ground.
Figure 1. Power Term 1SU1XXXX and 2SUXXX
Controllers
Figure 2. Power Term 1SU4XXXX and 1SU5XXX
Controllers
Power
Off
Record drive and
motor nameplate information including RPM, FLA and HP.
Check the drive and motor wiring, with an ohmeter on the
highest scale, for grounds. The ohmeter should read in
the Megaohm range or totally open. Check that the
incoming AC power is appropriate for the voltage as
stated on the nameplate of the drive.
Power
On
With motor not
wired to the drive, apply power. Drive will go through
its own software selftesting procedure for
approximately 5 seconds, and then display on the keypad
0.00. At this point you can press the start key on the
keypad.
If FL is displayed on the keypad LEDs, check that there
is either a wire or motor thermostat connected between
terminals 10, 11 (as shown in figure 3).
| WARNING |
| DRIVE HAS DC BUS
STORAGE CAPACITORS. WITH POWER APPLIED +/-
TERMINALS SHOULD=APPROXIMATELY 325 VDC FOR 230
VAC OR 650 VDC FOR 460 VAC DRIVE (AS SHOWN IN
FIGURES 1 AND2). |
Turn
off power, allow bus storage capacitors to discharge by
letting drive sit without power for 5 minutes or check DC
voltage on +/- terminals. Check motor wiring for the
appropriate voltage. Wire motor to U, V and W (as per
figure 1 and 2.)
Figure 3. Regulator Terminal
Strip
Running the
Drive
With motor
disconnected from the mechanical load, reapply power and
run the drive. With the drive in the local mode (from the
keypad), remote led off, press start key and observe
motor rotation. If motor rotation is incorrect, turn off
power and let bus caps discharge as above, change any two
motor leads (at U, V and W).
Run motor up and
down the speed range by pressing up/down arrow keys.
Connect motor to mechanical load and run drive throughout
speed range. Check monitor rpm, percentage load and
voltage using mode/enter key. Check calculation in
software section for function F14 motor thermal
overload.
Quick startup is complete.
If the
application requires remote start/stop or analog speed
reference read Section 5.0 Adjusting the Values of Drive
Functions and Typical Wiring Diagrams, Section 3.0
Installation
and Wiring.
Software
For most local
applications default values are acceptable as listed on
the attached parameter list.
To Change
Parameters
- Press
stop/reset key to stop the drive.
- Press
mode/enter key, Program LED should
light.
- Press
up/down arrow key until desired
function.
- Press
mode/enter button which display value within
function.
- Use
up/down keys to change parameter
content.
- Press
mode/enter button.
- Press
stop/reset button to exit programming
mode.
To View and
Clear Error Log
- Press
stop/reset key to stop the drive.
- Press
mode/enter button to enter program mode.
- Use
down arrow key until Err is displayed.
- Press
mode/enter keys to scroll through
errors.
- Press
stop/reset key to clear faults.
Possible
Faults
HU DC high bus
voltage condition
LU DC low bus
voltage condition
OL Electronic thermal
overload
OH Controller high
temperature
OC Overcurrent, short
circuit protection
FL External function
loss
Important
Parameters to Check
F00 Control source
select (0=local, 1=remote controlterminal speed
reference, 2=remote start/stop with keypad speed
reference, 3=remote tb start/stop with tb
multispeed presets)
F01 Accel time 0.5-30
seconds
F02 Decel time 0.5-30
seconds
F03 Minimum speed
F04 Maximum speed
F05 Current Limit
F08 RPM scaling at abase
speed (whatever you want display to read when drive
reaches F07)
F14 Elect thermal
overload = (motor overload fla/drive output fla) x
100
Monitoring
Speed, Current, Voltage, Percent Speed
Reference
While drive is
running press mode/enter key until desired LED is lit.
RPM LED displays output speed scaled by whatever is in
function F08. Percentage Load LED displays
percentage of controller fl output amps. Voltage LED
displays motor output voltage. With F13 set to on,
all these LEDs lit, displays remote reference
percentage
For Remote
Start/Stop via Terminal Board with Speed Pot
Reference
F-00=1
NOTES
- J6
Speed Ref
Pins 12 010 VDC
Pins 23 020 mA
- Output
010 VDC
Volts, RPM or Percent Load
Depending On Mode On
Mode/Enter Display
- Relay
Configurable
Function F09
0 Controller Running
1 IET Active
2 Drive at Speed
- Connection
Must Be
Made To Run
|
 |
For
MultiSpeed Application via Terminal Board with
Remote
Analog Ref and 3 MultiSpeed
Presets
F00=3 presets are
set with functions F23, F24 and F25 as
per table in note 5.
NOTES
- Open
= Stopped
Closed = IET Reset/Start
- Output
010 VDC
Volts, RPM or Percent Load
Depending On Mode On
Mode/Enter Display
- Relay
Configurable
Function F09
0 Controller Running
1 IET Active
2 Drive at Speed
- Connection
Must Be
Made To Run
|
 |
For Remote
Start/Stop via Terminal Board with Speed Pot
Reference.
F00=1
NOTES
- J6
Speed Ref
Pins 12 010 VDC
Pins 23 020 mA
- Output
010 VDC
Volts, RPM or Percent Load
Depending On Mode On
Mode/Enter Display
- Relay
Configurable
Function F09
0 Controller Running
1 IET Active
2 Drive at Speed
- Connection
Must Be
Made To Run
|
 |
SP500 I/M
D233041 Parameter
List
Function
|
Description
|
Range
|
Default
|
F00
|
CONTROL
SOURCE SELECT |
0 =
LOCAL
1 = REMOTE TB CONTROLS ANA REF
2 = REMOTE TB CONTROLS LOCAL REF
3 = REMOTE TB CONTROLS, MULTI SPD
PRESETS |
0
|
F01
|
ACCEL
RATE |
0.5-30
SECONDS |
5.0
|
F02
|
DECEL
RATE |
0.5-30
SECONDS |
5.0
|
F03
|
MINIMUM
SPEED |
0.5-30
Hz |
5.0
|
F04
|
MAXIMUM
SPEED |
30-240
Hz |
60
|
F05
|
CURRENT
LIMIT |
10-150
PERCENT |
150
|
F06
|
MAN
TORQUE BST |
2-10 |
2
|
F07
|
VOLTZ/HERTZ |
3-240
Hz |
60
|
F08
|
RPM
SCALING@BASE |
10-9999 |
1750
|
F09
|
CONFIG
OUTPUT RELAY |
0=CONTROLLER
RUNNING
1=IET ACTIVE
2=DRIVE AT SPEED |
0
|
F10
|
CARRIER
FREQ |
4,6,8
kHz |
4
|
F11
|
REMOTE
REF GAIN |
60-100% |
100
|
F12
|
REMOTE
REF OFFSET |
0-40% |
0
|
F13
|
PER
SEL SPD REF |
ON,
OFF ON=ENABLED |
OFF
|
F14
|
ELECTR
THERM OVLD |
20-100% |
100
|
F15
|
ELEC
THERM ENABLE |
OFF,
ON |
ON
|
F16
|
COAST
STOP ENABLE |
OFF,
ON |
ON
|
F17
|
REVERSE
DISABLE |
OFF,
ON |
OFF
|
F18
|
RPM
SETPOINT ENABLE |
OFF,
ON |
OFF
|
F19
|
POWERUP
START ENAB |
OFF,
ON |
OFF
|
F20
|
PASSWORD
LOCKOUT |
OFF,
ON |
OFF
|
F21
|
AVOIDANCE
FREQ |
MINMAX
FREQ |
5
|
F22
|
AVOIDANCE
BAND |
0-10.0
(HZ) |
0.0
|
F23
|
MULTISPD
PRESET |
MINMAX
FREQ |
20
|
F24
|
MULTISPD
PRESET 2 |
MINMAX
FREQ |
20
|
F25
|
MULTISPD
PRESET 3 |
MINMAX
FREQ |
20
|
F26
|
AUTO
RESTART NUMBER
ATTEMPTS |
0-10
RESETTABLE FAULTS
OVERTEMP - OT
OVERCURRENT - OC
HIGH BUS - HU
LOW BUS - LU
THERMAL OVERLOAD - OL |
0
|
F27
|
AUTO
RESTART RETRY WAIT TIME |
1-30
SECONDS |
1.0
|
F28
|
CONTROL
VOLTAGE |
INPUT
VOLTAGE DEPENDENT |
|
F49
|
SOFTWARE
VERSION |
|
|
ERR
|
ERROR
LOG |
|
|
Reliance
Company, 1995.
- Note: This material is not intended to provide
operational instructions.
- Appropriate Reliance Industrial
Company instruction manuals
and precautions should be studied prior to
installation, operation, or
maintenance of equipment.
|